Supply UGF open-air high-pressure rubber flexible cables
| Information Name: | Supply UGF open-air high-pressure rubber flexible cables |
| Published: | 2012-05-08 |
| Validity: | 30 |
| Specifications: | |
| Quantity: | 10000.00 |
| Price Description: | |
| Detailed Product Description: |
UGFP open-air high-pressure rubber soft cable, the UGF high pressure mine cable - open pit mine open GF cable uses high pressure rubber sheathed cables for: AC rated voltage 15kv and below, including 3.6/6kv.6/10kv 8.7/15kv mobile distribution equipment and mine mining machinery; hoisting and conveying machinery
Model and name: UGF-15KV mine with rubber sheathed flexible cables, performance standards: TL/J30-943 UGF cable use: AC rated voltage 15kv and below mobile power distribution unit and of mining machinery; hoisting and conveying machinery. 4 features: cable's rated voltage 10kv; long-term operating temperature of the cable to +90 ℃. Cable minimum bending radius is six times the cable diameter.
UGFP semi-conductive cloth with shield the cable jacket with neoprene or neoprene-based mixed rubber, oil resistance and does not extend to flammable for assessment. The cable specifications should meet the following requirements
Number of cores × cross-section conductor structure root / diameter insulated to a nominal thickness of the jacket nominal thickness of a nominal outside diameter wire main core DC resistance
Europe / km
6KVUGF cable parameters main core earth core
ugf 3 × 6 +1 × 6 84/0.30 4.5 1.4 6.0 40.3 3.30
ugf 3 × 10 +1 × 10 84/0.40 4.5 1.6 6.0 43.8 1.91
ugf 3 × 16 +1 × 16 126/0.40 4.5 1.6 6.0 46.8 1.21
ugf 3 × 25 +1 × 16 196/0.40 4.5 1.6 6.0 49.3 0.78
ugf 3 × 25 +1 × 16 276/0.40 4.5 1.6 6.0 52.0 0.554
6, 6KVUGF technical performance:
Conductor DC Resistance at 20 ° C see table above.
The insulation resistance between the finished UGFP cable core, which translates to a length of 1km, the temperature to 20 ° C, should not be less than 100 megohms.
The finished UGEP the main core of the cable and the main core and the ground wire, you should be able to withstand the AC 50 Hz 15 000 V voltage test of 5 minutes without breakdown.
7, delivery requirements:
The length of the cable delivery should not be less than 100m, the allowable length of not less than 20m
Short section of cable delivery, the delivery quantity shall not exceed the delivery of 10% of the total length of
The length measurement error should not exceed ± 0.5%.
|
|